Free generator load bank test record
Free generator load bank test record (PDF-ready). Documents resistive load test steps, voltage, frequency and NFPA 110 load test results.
Download free PDF template
Use in MapTrack →Trusted by teams across Australia and New Zealand
We respect your privacy. Unsubscribe anytime.
Updated 26 Oct 2026
Generator Load Bank Test Record
Annual load bank test record for standby generators | NFPA 110 load test results.
Load bank setup
Pre-start engine checks
25 percent load step
50 percent load step
75 percent load step
Full load endurance run
Step-down & shutdown
How to use: download the PDF, print or complete digitally on any device.
- PDF format, ready to print or fill on screen
- Use as-is or customise to suit your operation
- Go digital in MapTrack for photos, reminders and audit trails
Or set it up in MapTrack
- Fill it in on a phone, attach photos to any check
- Automatic reports and audit trails
- Upload the PDF and MapTrack drafts the form for you
Free trial. No credit card. Personal email accepted.
Don't just download it - use it live. Start a free workspace, upload this generator load bank test record and MapTrack drafts it as a form your crew can run from a phone.
Co-Founder & Commercial Director
Short answer
A generator load bank test record documents a load test on a standby generator: set-up, load steps such as 25, 50, 75 and 100 percent of rating, time at each step, and electrical and engine readings, with technician sign-off. Many facility managers test yearly with the annual service. NFPA 110 (2025 edition) clause 8.4.2.4 sets an annual supplemental load test for diesel sets that cannot meet the monthly exercise load.
Checked against NFPA 110, 2025 edition on by the MapTrack templates team. How we check templates
Key takeaways
- The MapTrack generator load bank test record contains 35 checks across 7 sections. Sections covered: Load bank setup, Pre-start engine checks, 25 percent load step, 50 percent load step, 75 percent load step, Full load endurance run, Step-down & shutdown.
- NFPA 110 clause 8.4.2: exercise generators at least monthly for at least 30 minutes, using one of the listed loading methods.
- Diesel sets that cannot meet the monthly loading need an annual supplemental load test at 50 then 75 percent (NFPA 110 clause 8.4.2.4).
- In Australia, model WHS Regulations reg 213 requires testing, where needed, by a competent person following the manufacturer's recommendations.
- AS/NZS 3010:2017 covers installing generating sets; it does not set a load test interval.
- Record readings at every load step, plus any shutdown, warning or abnormal reading and the corrective action taken.
Enter your email below to download this generator load bank test record as a ready-to-use PDF.
Used by construction, mining and field service teams
What is a generator load bank test record?
A generator load bank test record is a structured form used to document the results of a resistive load bank test on a standby diesel or gas generator. It captures the test set-up (load bank capacity connection method and step increments) the test load profile (typically 25 percent 50 percent 75 percent and 100 percent of rated output) and the readings recorded at each step (voltage frequency current kilowatts coolant temperature oil pressure exhaust temperature and ambient temperature). The record also notes the duration at each load step and the technician sign-off against the test procedure: NFPA 110 where it applies, the manufacturer instructions and the site maintenance schedule.
Standby generators that sit idle for most of their life accumulate unburnt fuel and carbon deposits in the exhaust system a condition known as wet stacking. A load bank test exercises the generator at or near its rated capacity which burns off these deposits restores rated output and proves the cooling system can sustain full thermal load. NFPA 110 (Standard for Emergency and Standby Power Systems) requires diesel sets to be exercised monthly for at least 30 minutes at not less than 30 percent of nameplate kW, or at the load that holds the manufacturer's minimum exhaust gas temperature. A diesel set that cannot meet that is also tested annually with supplemental load: 30 minutes at not less than 50 percent of nameplate, then 60 minutes at not less than 75 percent. Level 1 systems are also tested at least once every 36 months for their class duration, up to 4 hours. In Australia, AS/NZS 3010 covers the installation of generating sets rather than their testing, and regulation 213 of the WHS Regulations requires maintenance, inspection and, if necessary, testing by a competent person following the manufacturer's recommendations. AS 2941 covers fire pumpset systems, including the alternative power supply to an electric pumpset, and is not a standby generator testing standard. Maintaining a clean load bank test record per generator provides documented evidence that the asset is fit to carry life-safety load during an emergency and supports the compliance certificate renewal cycle.
Learn more about maintenance and work orders in MapTrack.
Keeping load bank test records for several generators? See how a digital check works on our asset inspection software page.
Get the free template
Enter your email above to download the full generator load bank test record as a PDF.
Benefits of using this generator load bank test record
- Wet stacking prevention: a sustained load bank test burns off unburnt fuel and carbon deposits that accumulate during low-load monthly exercising and restores rated output
- NFPA 110 test records: documents the annual supplemental load test NFPA 110 requires for diesel sets that cannot meet the monthly loading, the 36-month test for Level 1 systems, and any load testing the manufacturer specifies
- Cooling system validation: extended operation at 75 to 100 percent rated load verifies the radiator fan and coolant system can sustain full thermal load without overheating
- Performance baseline: records voltage frequency kilowatts and temperatures at each load step creating a year-on-year baseline that reveals slow degradation in alternator or engine performance
- Insurance and compliance certificate: completed load bank records support renewal of the building compliance certificate and protect building owners from liability after a generator failure during a real emergency
- Fault detection at load: cooling fuel delivery and electrical issues that do not appear during a 30-minute monthly test often surface during a sustained load bank run before they cause a real-world fail-to-run event
Benefits of digitising forms in MapTrack
When you digitise generator records in MapTrack, you get:
- Field users can easily scan a QR code to complete a form on mobile. Unlimited users.
- Email the right people when a form is submitted, with an automation you set up.
- File every completed form against the asset, location or person it covers.
- Download any completed form as a PDF, with failed answers listed at the top.
- Fill in forms offline; they upload when the device is back online.
- Build conditional logic (show or hide questions based on answers).
- Take pictures or attach photos. Not possible with a paper-based form.
- Electronic signatures.
- Edit forms later without reprinting.
- Set who can view, fill in or edit forms with user roles.
- Upload a paper form (PDF, Word, Excel or a photo) and MapTrack's AI builds a digital version for you to check.
- Raise a work order from a submitted form with an automation you set up.
- Track service intervals by hours, kilometres or calendar date in one place.
- Attach supplier invoices and parts receipts to each maintenance record.

Generators serviced on hours
A generator's service plan counting down the run hours to its 250 hour service.
MapTrack app · Demonstration data · Recorded
Book a demo to see how MapTrack handles generator records.
Try MapTrack free
Full access to every feature. No credit card required. Per-asset pricing so you scale as your fleet grows.
- No credit card required
1-2 days/week saved
“Bloody amazing! We used to spend 1-2 days a week tracking and managing our generators alone.”
Steve McAllister
Asset Coordinator, Saunders International
What to include in a generator load bank test record
This generator load bank test record covers 9 key areas:
- Generator details: ID make model serial number rated output (kW and kVA) voltage configuration year of manufacture and engine model
- Test set-up: load bank model capacity (kW) connection point (load bank breaker or generator terminals) cable size and routing and ambient conditions
- Pre-test checks: engine oil coolant fuel level fuel filter water separator battery voltage and block heater operation recorded before start
- Test load profile: load steps applied (typically 25 50 75 100 percent), duration at each step and the sustained run (the NFPA 110 annual supplemental test is 30 minutes at not less than 50 percent then 60 minutes at not less than 75 percent of nameplate)
- Engine readings: oil pressure coolant temperature exhaust temperature fuel pressure crankcase pressure and engine vibration at each load step
- Alternator readings: voltage (each phase) frequency current (each phase) kilowatts power factor and voltage regulator response at each load step
- Ambient conditions: generator room temperature humidity and ventilation airflow recorded at start mid-test and end
- Exceptions and shutdowns: any safety shutdowns warnings or abnormal readings during the test with corrective actions taken
- Sign-off: technician name licence (where applicable) building owner or facility manager witness signature date and next load test due
How to use this generator load bank test record
- Plan the test and notify building stakeholders: confirm the generator rating and the corresponding load bank capacity required. Notify building management security and any tenants connected to the generator transfer switch at least 48 hours in advance. Schedule the test for a low occupancy period and confirm the technician holds the required electrical licence for the jurisdiction
- Set up the load bank and connect to the generator: position the load bank with adequate ventilation clearance per the manufacturer specification and connect to the generator load terminals or downstream load bank breaker using correctly rated cables. Verify the load bank emergency stop and step controls are operational and that the resistive elements are at ambient temperature before start
- Conduct pre-test checks: record the generator hour meter ambient temperature engine oil and coolant levels fuel quantity battery voltage and block heater temperature. Confirm there are no active alarms on the controller and that the manual or remote start sequence is ready. Take an initial set of static readings before applying load
- Apply load in stepped increments: start the generator and allow it to reach rated speed. Apply load in 25 percent increments allowing 15 to 30 minutes at each step. Record voltage (each phase) frequency current (each phase) kilowatts power factor coolant temperature oil pressure and exhaust temperature at each step. Watch for voltage droop frequency instability or temperature excursions outside the manufacturer envelope
- Sustain the test load period: hold the load for the duration the test calls for: the NFPA 110 annual supplemental test is 30 minutes at not less than 50 percent then 60 minutes at not less than 75 percent of nameplate, and the 36-month Level 1 test runs for the class duration, up to 4 hours. Record readings every 15 minutes throughout the sustained run. Monitor coolant temperature and oil pressure continuously and respond to any safety alarm immediately by reducing load
- Step down test the alarms and complete sign-off: reduce load in reverse steps allow a 5-minute cool-down at no load then shut the generator down. Verify all controller alarms are clear and record any defects observations or recommendations on the load test record. The technician building owner or facility manager signs and dates the record and sets the next load bank test due date in MapTrack
In MapTrack, you can schedule and track maintenance digitally, by date or meter reading. Each submission is stored as a timestamped PDF against the asset record.
Get the free templateEnter your email above to download the full generator load bank test record as a PDF.Back to download formHow often should you complete this record?
NFPA 110 (Standard for Emergency and Standby Power Systems) sets a monthly exercise for diesel sets of at least 30 minutes at not less than 30 percent of nameplate kW, or at the load that holds the manufacturer's minimum exhaust gas temperature. A diesel set that cannot reach that load each month is tested annually with supplemental load, and Level 1 systems also get a test at least once every 36 months for their class duration, up to 4 hours. In Australia, regulation 213 of the WHS Regulations requires maintenance, inspection and, if necessary, testing to follow the manufacturer's recommendations; AS/NZS 3010 is the installation standard for generating sets and does not set a test interval. Many facility managers schedule a load bank test every 12 months as part of the annual service.
A monthly run on light building load is not a substitute for a load bank test, because a diesel set that runs below its minimum load builds up unburnt fuel (wet stacking); that is why NFPA 110 adds the annual supplemental load test for sets that cannot meet the monthly loading. Generators with high run hours in actual emergencies may justify additional load bank testing on a quarterly basis. In MapTrack the load test record can be attached to the generator asset with automated reminders set against calendar intervals and run hours.
Try MapTrack free
Full access to every feature. No credit card required. Per-asset pricing so you scale as your fleet grows.
- No credit card required
Frequently asked questions
What standards require annual generator load bank testing?
Why is a load bank test necessary if the generator is exercised monthly?
What load profile is used in a generator load bank test?
Who can perform a generator load bank test?
What readings must be recorded during a load bank test?
Applicable regulatory standards
This template is a starting point. Check the current requirements that apply to your equipment, work and location. The template alone does not establish compliance.
| Standard | Edition | Clauses this template relies on | Source |
|---|---|---|---|
| Standard for Emergency and Standby Power SystemsMonthly exercising, the annual supplemental load test, Level 1 testing and test records. | NFPA 110, 2025 edition |
| National Fire Protection Association (NFPA)Sold by the publisher |
| Model Work Health and Safety RegulationsAustralia: testing, where needed, by a competent person following the manufacturer's recommendations. | Model WHS Regulations as at 5 December 2025 (cited within as the Work Health and Safety Regulations 2011) |
| Safe Work Australia (drafted by the Parliamentary Counsel's Committee) |
| Electrical installations - Generating setsInstallation of generating sets, including those supplying safety services; it does not set a load test interval. | AS/NZS 3010:2017 (incl. Amd 1:2020) |
| Standards Australia and Standards New ZealandSold by the publisher |
Standard for Emergency and Standby Power Systems
Edition: NFPA 110, 2025 edition
Monthly exercising, the annual supplemental load test, Level 1 testing and test records.
- Chapter 8: Routine maintenance and operational testing of emergency power supply systems, including manuals, inspection, exercising, load tests and records.
- 8.4.2: Generators in service exercised at least monthly for at least 30 minutes, using one of the listed loading methods.
- 8.4.2.4: Diesel sets that cannot meet the monthly loading are exercised monthly and load tested annually with supplemental load at 50 and 75 percent.
- 8.4.9: Level 1 emergency power supply systems tested at least once in every 36 months.
- 8.5: Records of maintenance, inspection and testing of the emergency power supply system.
National Fire Protection Association (NFPA)Sold by the publisher
Model Work Health and Safety Regulations
Edition: Model WHS Regulations as at 5 December 2025 (cited within as the Work Health and Safety Regulations 2011)
Australia: testing, where needed, by a competent person following the manufacturer's recommendations.
- reg 213: Plant must be maintained, inspected and, if necessary, tested by a competent person, following manufacturer or competent person recommendations; annual inspection applies only if neither is practicable.
Safe Work Australia (drafted by the Parliamentary Counsel's Committee)
Electrical installations - Generating sets
Edition: AS/NZS 3010:2017 (incl. Amd 1:2020)
Installation of generating sets, including those supplying safety services; it does not set a load test interval.
- 3.5: Additional requirements for permanently connected generating sets supplying safety and essential services
Standards Australia and Standards New ZealandSold by the publisher
Each source was read at its publisher and the page checked on 26 October 2026. The publisher's current text is the authority.
Check the current source
Generator load bank test record preview

The numbers behind this generator load bank test record
The pages below gather the figures behind this kind of check. Each figure on them carries its source and date, so you can quote it in a toolbox talk, a budget case or a board paper without chasing the original report.
Get the free template
Enter your email above to download the full generator load bank test record as a PDF.
Embed this free template on your website
Run an industry blog, trade association site, or training resource? Drop a preview of this free generator load bank test record straight into your page. The snippet is self-contained, needs no scripts, and links readers back to the full free template.
<div style="max-width:480px;font-family:system-ui,-apple-system,'Segoe UI',Roboto,sans-serif;border:1px solid #E5E7EB;border-radius:12px;padding:20px;background:#ffffff;">
<p style="font-size:12px;font-weight:700;letter-spacing:0.05em;text-transform:uppercase;color:#071D49;margin:0;">Free template</p>
<p style="font-size:18px;font-weight:700;color:#071D49;margin:6px 0 0;">Generator load bank test record</p>
<ul style="margin:12px 0 0;padding-left:18px;color:#374151;font-size:14px;line-height:1.6;">
<li style="margin:4px 0;">Generator details: ID make model serial number rated output (kW and kVA) voltage configuration year of manufacture and engine model</li>
<li style="margin:4px 0;">Test set-up: load bank model capacity (kW) connection point (load bank breaker or generator terminals) cable size and routing and ambient conditions</li>
<li style="margin:4px 0;">Pre-test checks: engine oil coolant fuel level fuel filter water separator battery voltage and block heater operation recorded before start</li>
<li style="margin:4px 0;">Test load profile: load steps applied (typically 25 50 75 100 percent), duration at each step and the sustained run (the NFPA 110 annual supplemental test is 30 minutes at not less than 50 percent then 60 minutes at not less than 75 percent of nameplate)</li>
<li style="margin:4px 0;">Engine readings: oil pressure coolant temperature exhaust temperature fuel pressure crankcase pressure and engine vibration at each load step</li>
<li style="margin:4px 0;">Alternator readings: voltage (each phase) frequency current (each phase) kilowatts power factor and voltage regulator response at each load step</li>
</ul>
<p style="font-size:13px;color:#6B7280;margin:14px 0 0;padding-top:12px;border-top:1px solid #E5E7EB;">Free <a href="https://www.maptrack.com/templates/generator-load-bank-test-record" style="color:#071D49;font-weight:600;text-decoration:none;">Generator load bank test record</a> by MapTrack</p>
</div>Free to reuse, including commercially. This template is published under a Creative Commons Attribution 4.0 licence. Copy it, adapt it, put it on your own site or in your own docs. All we ask is that you credit MapTrack with a link back to this page. The snippet above already includes that credit, so if you use it as-is you’re covered.
Cite this template
Writing about this topic? You’re welcome to quote this checklist. Here’s the wording to use so your readers can find the original.
The MapTrack generator load bank test record contains 35 checks across 7 sections.
- Short attribution
- MapTrack Generator load bank test record, https://www.maptrack.com/templates/generator-load-bank-test-record
- Reference list
- MapTrack. (2026). Generator load bank test record [Checklist template]. Retrieved from https://www.maptrack.com/templates/generator-load-bank-test-record
Free to reuse with credit under a Creative Commons Attribution 4.0 licence. If you’d rather link straight to it, the page is https://www.maptrack.com/templates/generator-load-bank-test-record.
Need to schedule and track maintenance digitally, by date or meter reading?
Register every generator in MapTrack, attach digital forms, and get a complete history of every inspection, service and compliance record.
Maintenance and work orders · All templates · Pricing · Book a demo


