Fire Extinguisher 5-Year Hydrostatic Test Record
Hydrostatic pressure test record for the AS 1851-2012 five-yearly service
1. Pre-Test Condition Assessment
2. Depressurisation and Discharge
3. Internal Inspection
4. Hydrostatic Pressure Test
5. Post-Test and Recharge
6. Certification
How to use: download the PDF, print or complete digitally on any device.
- PDF format, ready to print or fill on screen
- Use as-is or customise to suit your operation
- Go digital in MapTrack for photos, reminders and audit trails
Or set it up in MapTrack
- Fill it in on a phone, attach photos to any check
- Automatic reports and audit trails
- The same checks as the PDF, ready to configure
Free trial. No credit card. Personal email accepted.
Don't just download it - use it live. Start a free workspace with this fire extinguisher 5-year hydrostatic test record already built, so your crew can run it from a phone.
Co-Founder & Commercial Director
Short answer
A fire extinguisher 5-year test record documents the five-yearly service of each portable extinguisher: condition on arrival, discharge, internal inspection, any pressure test and its result, recharge and return to service. AS 1851-2012 clause 10.4 sets six-monthly, yearly and five-yearly service. Whether the cylinder is pressure tested depends on the extinguisher type, so confirm the test with your service provider.
Checked against AS 1851-2012 (incl. Amd 1:2016) on by the MapTrack templates team. How we check templates
Key takeaways
- The MapTrack fire extinguisher 5-year hydrostatic test record contains 30 checks across 6 sections. Sections covered: 1. Pre-Test Condition Assessment, 2. Depressurisation and Discharge, 3. Internal Inspection, 4. Hydrostatic Pressure Test, 5. Post-Test and Recharge, 6. Certification.
- AS 1851-2012 clause 10.4 sets six-monthly, yearly and five-yearly service for portable extinguishers; a monthly visual check is site practice.
- A CO2 extinguisher's cylinder is a gas cylinder with its own test regime, so ask the service provider which test applies.
- AS 1851-2012 clause 10.2.8 deals with pressure test marking; record the test date against each extinguisher ID.
- A cylinder that fails is withdrawn, and a replacement of the right type goes in the same location (AS 2444).
- The work is done by a competent person (AS 1851-2012 clause 1.10) holding any licence your state requires.
Enter your email below to download this fire extinguisher 5-year hydrostatic test record as a ready-to-use PDF.
Used by construction, mining and field service teams
What is a fire extinguisher 5-year hydrostatic test record?
A fire extinguisher 5-year hydrostatic test record documents the results of pressure testing on portable fire extinguishers. AS 1851-2012 (Routine service of fire protection systems and equipment) includes a five-yearly service for portable extinguishers (clause 10.4.3). What that service involves, and whether the cylinder itself is pressure tested, depends on the extinguisher type, so confirm with your service provider which test applies to each unit. The test verifies the structural integrity of the cylinder under pressure.
The test involves depressurising and discharging the extinguisher, conducting a thorough internal inspection for corrosion or pitting, then filling the cylinder with water and pressurising it to the specified test pressure. The technician measures both elastic expansion and permanent expansion. If permanent expansion exceeds 10% of elastic expansion, the cylinder has deformed beyond safe limits and must be condemned and destroyed. This record captures every step of the process, from initial condition assessment through to recharging and recertification, ensuring full traceability for building compliance audits and Essential Safety Measures (ESM) annual statements.
Learn more about compliance and inspections in MapTrack.
Running five-yearly pressure tests on extinguishers? See extinguisher tracking for fire contractors with each cylinder's test dates on its own record.
Get the free template
Enter your email above to download the full fire extinguisher 5-year hydrostatic test record as a PDF.
Benefits of using this fire extinguisher 5-year hydrostatic test record
- Five-yearly service record: documents the pressure test done at an extinguisher's AS 1851-2012 five-yearly service, where its type calls for one, as evidence for the annual fire safety statement or report your state requires.
- Structural safety assurance: hydrostatic testing identifies weakened cylinders that may rupture under operating pressure, preventing catastrophic failure that could injure building occupants.
- Clear pass/fail criteria: the 10% permanent expansion threshold provides an objective, measurable standard that removes ambiguity from the condemn-or-return decision.
- Traceability and audit trail: records the technician licence number, test equipment calibration details and exact expansion measurements, creating a defensible audit trail.
- Lifecycle tracking: links each test to the extinguisher serial number and date of manufacture, enabling accurate scheduling of the next 5-year test.
- Site fire safety register integration: prompts the technician to update the building fire safety register immediately after testing, keeping the facility manager informed.
Benefits of digitising forms in MapTrack
When you move your checklists from paper to MapTrack, you get:
- Field users can easily scan a QR code to complete a form on mobile. Unlimited users.
- Email the right people when a form is submitted, with an automation you set up.
- File every completed form against the asset, location or person it covers.
- Download any completed form as a PDF, with failed answers listed at the top.
- Fill in forms offline; they upload when the device is back online.
- Build conditional logic (show or hide questions based on answers).
- Take pictures or attach photos. Not possible with a paper-based form.
- Electronic signatures.
- Edit forms later without reprinting.
- Set who can view, fill in or edit forms with user roles.
- Upload a paper form (PDF, Word, Excel or a photo) and MapTrack's AI builds a digital version for you to check.
- Schedule fire extinguisher, hydrant and alarm inspections, with an email to the assigned person in the week before each is due.
- Track emergency evacuation drill records and corrective actions per site.
- Keep a digital fire safety register, with every inspection filed against its asset or site.

Extinguisher checks on schedule
The Service Board filtered to extinguisher checks, with the overdue ones first.
MapTrack app · Demonstration data · Recorded
See how MapTrack handles checklists: Fire equipment register →
Try MapTrack free
Full access to every feature. No credit card required. Per-asset pricing so you scale as your fleet grows.
- No credit card required
Less loss and downtime
“Doing monthly site audits in MapTrack has drastically reduced our equipment loss and downtime.”

Khalid El-Hussein
NSW Store Manager, Axis Services Group
What to include in a fire extinguisher 5-year hydrostatic test record
This fire extinguisher 5-year hydrostatic test record covers 10 key areas:
- Extinguisher identification: asset number, serial number, type, capacity, manufacturer and date of manufacture.
- Technician name and fire protection licence number.
- Pre-test external condition assessment: corrosion, dents, pressure gauge, safety pin, tamper seal, hose and label.
- Depressurisation and discharge confirmation with empty cylinder weight.
- Internal inspection: cylinder walls, valve threads, siphon tube, internal coating.
- Hydrostatic test: test pressure applied (kPa), elastic expansion (mL), permanent expansion (mL), percentage calculation.
- Pass or condemn result with action taken.
- Post-test recharge: correct agent, correct pressure, gauge verification, cylinder re-stamp.
- Service tag attachment and fire safety register update.
- Test certificate issuance confirmation.
How to use this fire extinguisher 5-year hydrostatic test record
- Conduct a thorough pre-test external condition assessment.: Inspect the cylinder for corrosion, dents, bulging and damage. Check the pressure gauge reading, safety pin, tamper seal, hose condition, nozzle and label legibility. Record the extinguisher type, capacity and date of manufacture. If the external condition shows severe damage, condemn without proceeding to hydrostatic test.
- Safely depressurise, discharge and disassemble the extinguisher.: Depressurise the cylinder safely following the manufacturer procedure. Discharge all remaining agent into an approved container. Remove the valve assembly and weigh the empty cylinder, recording the tare weight for comparison against manufacturer specifications.
- Perform a detailed internal inspection of the cylinder.: Use a borescope or light source to examine internal cylinder walls for corrosion, pitting, scoring and thinning. Inspect valve threads for damage. Check the siphon tube and dip tube for deterioration. Examine any internal coating or lining for delamination. If significant internal damage is found, condemn the unit without proceeding to hydrostatic test.
- Fill the cylinder with water and perform the hydrostatic pressure test.: Fill the cylinder completely with water, eliminating all air. Connect to calibrated hydrostatic test equipment. Pressurise to the specified test pressure and hold for a minimum of 60 seconds. Measure elastic expansion during pressurisation and permanent expansion after release. Calculate permanent expansion as a percentage of elastic expansion.
- Determine the result and complete post-test actions.: If permanent expansion exceeds 10% of elastic expansion, the extinguisher fails and must be condemned and destroyed by the technician. If it passes, drain and dry the cylinder thoroughly, reassemble the valve, recharge with the correct agent to the correct pressure, verify the gauge reads in the green zone, and re-stamp the cylinder with the new test date.
- Complete certification and update all records.: Attach a new service tag showing the test date and next due date. Update the building fire safety register with the test result. Issue a formal test certificate to the site fire warden or facility manager. Record condemned and destroyed units in the register with replacement details.
In MapTrack, you can manage fire safety inspections and equipment checks digitally. Each submission is stored as a timestamped PDF against the asset record.
Get the free templateEnter your email above to download the full fire extinguisher 5-year hydrostatic test record as a PDF.Back to download formHow often should you complete this checklist?
AS 1851-2012 sets six-monthly, yearly and five-yearly service for portable extinguishers, with a three-yearly item in clause 10.2.3. There is no single pressure-test interval for every extinguisher: what the five-yearly service involves, and whether the cylinder is pressure tested, depends on the type, and a CO2 cylinder is a gas cylinder with its own test regime, so ask your service provider what applies to each unit. The clock starts from the date of manufacture stamped on the cylinder, not from the date of installation. A monthly visual check between services is site practice, not an AS 1851 frequency. In MapTrack, you can set each extinguisher's test schedule against its asset record, and the assigned person gets an email in the week before each test falls due, across all your sites.
Try MapTrack free
Full access to every feature. No credit card required. Per-asset pricing so you scale as your fleet grows.
- No credit card required
Frequently asked questions
What happens if a fire extinguisher fails the hydrostatic test?
Who is qualified to perform hydrostatic testing on fire extinguishers?
How does the 5-year hydrostatic test differ from the 6-monthly routine service?
Do CO2 extinguishers require hydrostatic testing at a different interval?
How long should the hydrostatic test certificate be retained?
Applicable regulatory standards
This template is a starting point. Check the current requirements that apply to your equipment, work and location. The template alone does not establish compliance.
| Standard | Edition | Clauses this template relies on | Source |
|---|---|---|---|
| Routine service of fire protection systems and equipmentRoutine service of portable extinguishers, including the five-yearly service and pressure test marking, done by competent people, with service records. | AS 1851-2012 (incl. Amd 1:2016) |
| Standards AustraliaSold by the publisher |
| Portable fire extinguishers, Part 1: General requirementsGeneral product requirements for portable fire extinguishers. | AS/NZS 1841.1:2007 | Whole instrument | Standards AustraliaSold by the publisher |
| Portable fire extinguishers and fire blankets - Selection and locationSelecting and locating extinguishers, used when a failed unit is replaced. | AS 2444-2001 |
| Standards AustraliaSold by the publisher |
| Environmental Planning and Assessment (Development Certification and Fire Safety) Regulation 2021 (NSW)NSW owners keep essential fire safety measures, such as extinguishers, maintained to their standard of performance. | Environmental Planning and Assessment (Development Certification and Fire Safety) Regulation 2021 (NSW), text as at 12 August 2023 |
| NSW Parliamentary Counsel's Office (NSW Legislation) |
| Building Regulations 2018 (Vic)Victorian essential safety measures maintenance and the annual report the record supports. | Building Regulations 2018 (Vic), version 031 (in force from 1 September 2026) |
| Victorian Government (Victorian Legislation) |
Routine service of fire protection systems and equipment
Edition: AS 1851-2012 (incl. Amd 1:2016)
Routine service of portable extinguishers, including the five-yearly service and pressure test marking, done by competent people, with service records.
- Section 10: Routine service of portable and wheeled fire extinguishers.
- 1.10: Competence required of people who carry out routine service.
- 1.16: Routine service records: logbooks, tags and labels, summary records and record retention.
- 10.4: Routine service schedules for portable fire extinguishers, including yearly and five-yearly service.
- 10.2.8: Pressure test marking of fire extinguishers.
Standards AustraliaSold by the publisher
Portable fire extinguishers, Part 1: General requirements
Edition: AS/NZS 1841.1:2007
General product requirements for portable fire extinguishers.
Standards AustraliaSold by the publisher
Portable fire extinguishers and fire blankets - Selection and location
Edition: AS 2444-2001
Selecting and locating extinguishers, used when a failed unit is replaced.
- Section 2: Selection of portable fire extinguishers.
- Section 3: Location of portable fire extinguishers.
Standards AustraliaSold by the publisher
Environmental Planning and Assessment (Development Certification and Fire Safety) Regulation 2021 (NSW)
Edition: Environmental Planning and Assessment (Development Certification and Fire Safety) Regulation 2021 (NSW), text as at 12 August 2023
NSW owners keep essential fire safety measures, such as extinguishers, maintained to their standard of performance.
- s 81: Requires the building owner to keep each essential fire safety measure maintained to its standard of performance.
Building Regulations 2018 (Vic)
Edition: Building Regulations 2018 (Vic), version 031 (in force from 1 September 2026)
Victorian essential safety measures maintenance and the annual report the record supports.
- reg 216: Requires the owner to comply with the maintenance determination for essential safety measures.
- reg 223: Requires the owner to prepare an annual essential safety measures report.
Each source was read at its publisher and the page checked on 26 October 2026. The publisher's current text is the authority.
Fire extinguisher 5-year hydrostatic test record preview

The numbers behind this fire extinguisher 5-year hydrostatic test record
The pages below gather the figures behind this kind of check. Each figure on them carries its source and date, so you can quote it in a toolbox talk, a budget case or a board paper without chasing the original report.
Get the free template
Enter your email above to download the full fire extinguisher 5-year hydrostatic test record as a PDF.
Embed this free template on your website
Run an industry blog, trade association site, or training resource? Drop a preview of this free fire extinguisher 5-year hydrostatic test record straight into your page. The snippet is self-contained, needs no scripts, and links readers back to the full free template.
<div style="max-width:480px;font-family:system-ui,-apple-system,'Segoe UI',Roboto,sans-serif;border:1px solid #E5E7EB;border-radius:12px;padding:20px;background:#ffffff;">
<p style="font-size:12px;font-weight:700;letter-spacing:0.05em;text-transform:uppercase;color:#071D49;margin:0;">Free template</p>
<p style="font-size:18px;font-weight:700;color:#071D49;margin:6px 0 0;">Fire extinguisher 5-year hydrostatic test record</p>
<ul style="margin:12px 0 0;padding-left:18px;color:#374151;font-size:14px;line-height:1.6;">
<li style="margin:4px 0;">Extinguisher identification: asset number, serial number, type, capacity, manufacturer and date of manufacture.</li>
<li style="margin:4px 0;">Technician name and fire protection licence number.</li>
<li style="margin:4px 0;">Pre-test external condition assessment: corrosion, dents, pressure gauge, safety pin, tamper seal, hose and label.</li>
<li style="margin:4px 0;">Depressurisation and discharge confirmation with empty cylinder weight.</li>
<li style="margin:4px 0;">Internal inspection: cylinder walls, valve threads, siphon tube, internal coating.</li>
<li style="margin:4px 0;">Hydrostatic test: test pressure applied (kPa), elastic expansion (mL), permanent expansion (mL), percentage calculation.</li>
</ul>
<p style="font-size:13px;color:#6B7280;margin:14px 0 0;padding-top:12px;border-top:1px solid #E5E7EB;">Free <a href="https://www.maptrack.com/templates/fire-extinguisher-5-year-test" style="color:#071D49;font-weight:600;text-decoration:none;">Fire extinguisher 5-year hydrostatic test record</a> by MapTrack</p>
</div>Free to reuse, including commercially. This template is published under a Creative Commons Attribution 4.0 licence. Copy it, adapt it, put it on your own site or in your own docs. All we ask is that you credit MapTrack with a link back to this page. The snippet above already includes that credit, so if you use it as-is you’re covered.
Cite this template
Writing about this topic? You’re welcome to quote this checklist. Here’s the wording to use so your readers can find the original.
The MapTrack fire extinguisher 5-year hydrostatic test record contains 30 checks across 6 sections.
- Short attribution
- MapTrack Fire extinguisher 5-year hydrostatic test record, https://www.maptrack.com/templates/fire-extinguisher-5-year-test
- Reference list
- MapTrack. (2026). Fire extinguisher 5-year hydrostatic test record [Checklist template]. Retrieved from https://www.maptrack.com/templates/fire-extinguisher-5-year-test
Free to reuse with credit under a Creative Commons Attribution 4.0 licence. If you’d rather link straight to it, the page is https://www.maptrack.com/templates/fire-extinguisher-5-year-test.
Need to manage fire safety inspections and equipment checks digitally?
Register every asset in MapTrack, attach digital forms, and get a complete history of every inspection, service and compliance record.
Compliance and inspections · All templates · Pricing · Book a demo