Free fire extinguisher 5-year hydrostatic test record

Free fire extinguisher 5-year hydrostatic test record for the AS 1851-2012 five-yearly service. Internal inspection, pressure test and pass/condemn sign-off.

Updated 12 Oct 2026

Fire Extinguisher 5-Year Hydrostatic Test Record

Hydrostatic pressure test record for the AS 1851-2012 five-yearly service

Live form
0 of 30 checks

1. Pre-Test Condition Assessment

1Cylinder external condition (corrosion, dents, damage)
2Pressure gauge reading
3Safety pin and tamper seal
4Hose and nozzle condition
5Label legibility
6Mounting bracket condition

2. Depressurisation and Discharge

7Depressurise cylinder safely
8Discharge all contents
9Remove valve assembly
10Weigh empty cylinder and record

3. Internal Inspection

11Internal cylinder walls (corrosion, pitting, scoring)
12Valve thread condition
13Siphon tube condition (if fitted)
14Dip tube condition
15Internal coating/lining (if applicable)

4. Hydrostatic Pressure Test

16Fill cylinder with water
17Pressurise to test pressure
18Hold for 60 seconds minimum
19Measure elastic expansion
20Measure permanent expansion
21Permanent expansion must not exceed 10% of elastic expansion - PASS/FAIL

5. Post-Test and Recharge

22Drain and dry cylinder thoroughly
23Reassemble valve
24Recharge with correct agent and pressure
25Verify pressure gauge in green zone
26Re-stamp cylinder with test date

6. Certification

27Attach new service tag
28Update fire safety register
29Condemn and destroy if failed
30Issue test certificate

How to use: download the PDF, print or complete digitally on any device.

  • PDF format, ready to print or fill on screen
  • Use as-is or customise to suit your operation
  • Go digital in MapTrack for photos, reminders and audit trails

Download free PDF template

Use in MapTrack →
FreePDFUpdated Oct 2026

Get your free template

Enter your email to download the fire extinguisher 5-year hydrostatic test record as a free PDF. No sign-up required to use it.

Your info is secure. No spam, ever.

These templates are free general guides provided as-is. They do not constitute legal, safety or compliance advice. You are responsible for ensuring any form meets your specific workplace obligations, industry standards and applicable regulations.

Trusted by teams across Australia and New Zealand

We respect your privacy. Unsubscribe anytime.

Or set it up in MapTrack

  • Fill it in on a phone, attach photos to any check
  • Automatic reports and audit trails
  • The same checks as the PDF, ready to configure

Free 30-day trial. No credit card. Personal email accepted.

Don't just download it - use it live. Start a free workspace with this fire extinguisher 5-year hydrostatic test record already built, so your crew can run it from a phone.

Jarrod Milford

Jarrod Milford

Co-Founder & Commercial Director

Updated 12 October 2026

Key takeaways

  • The MapTrack fire extinguisher 5-year hydrostatic test record contains 30 checks across 6 sections. Sections covered: 1. Pre-Test Condition Assessment, 2. Depressurisation and Discharge, 3. Internal Inspection, 4. Hydrostatic Pressure Test, 5. Post-Test and Recharge, 6. Certification.

Enter your email below to download this fire extinguisher 5-year hydrostatic test record as a ready-to-use PDF.

Used by construction, mining and field service teams

Saunders InternationalMineral ResourcesSupagasHacer GroupMetro TunnelUltrabuilt

What is a fire extinguisher 5-year hydrostatic test record?

A fire extinguisher 5-year hydrostatic test record documents the results of pressure testing on portable fire extinguishers. AS 1851-2012 (Routine service of fire protection systems and equipment) includes a five-yearly service for portable extinguishers (clause 10.4.3). What that service involves, and whether the cylinder itself is pressure tested, depends on the extinguisher type, so confirm with your service provider which test applies to each unit. The test verifies the structural integrity of the cylinder under pressure.

The test involves depressurising and discharging the extinguisher, conducting a thorough internal inspection for corrosion or pitting, then filling the cylinder with water and pressurising it to the specified test pressure. The technician measures both elastic expansion and permanent expansion. If permanent expansion exceeds 10% of elastic expansion, the cylinder has deformed beyond safe limits and must be condemned and destroyed. This record captures every step of the process, from initial condition assessment through to recharging and recertification, ensuring full traceability for building compliance audits and Essential Safety Measures (ESM) annual statements.

Learn more about compliance and inspections in MapTrack.

Benefits of using this fire extinguisher 5-year hydrostatic test record

  • Five-yearly service record: documents the pressure test done at an extinguisher's AS 1851-2012 five-yearly service, where its type calls for one, as evidence for the annual fire safety statement or report your state requires.
  • Structural safety assurance: hydrostatic testing identifies weakened cylinders that may rupture under operating pressure, preventing catastrophic failure that could injure building occupants.
  • Clear pass/fail criteria: the 10% permanent expansion threshold provides an objective, measurable standard that removes ambiguity from the condemn-or-return decision.
  • Traceability and audit trail: records the technician licence number, test equipment calibration details and exact expansion measurements, creating a defensible audit trail.
  • Lifecycle tracking: links each test to the extinguisher serial number and date of manufacture, enabling accurate scheduling of the next 5-year test.
  • Site fire safety register integration: prompts the technician to update the building fire safety register immediately after testing, keeping the facility manager informed.

Benefits of digitising forms in MapTrack

When you move your checklists from paper to MapTrack, you get:

  • Field users can easily scan a QR code to complete a form on mobile. Unlimited users.
  • Email the right people when a form is submitted, with an automation you set up.
  • File every completed form against the asset, location or person it covers.
  • Download any completed form as a PDF, with failed answers listed at the top.
  • Fill in forms offline; they upload when the device is back online.
  • Build conditional logic (show or hide questions based on answers).
  • Take pictures or attach photos. Not possible with a paper-based form.
  • Electronic signatures.
  • Edit forms later without reprinting.
  • Set who can view, fill in or edit forms with user roles.
  • Upload a paper form (PDF, Word, Excel or a photo) and MapTrack's AI builds a digital version for you to check.
  • Schedule fire extinguisher, hydrant and alarm inspections, with an email to the assigned person in the week before each is due.
  • Track emergency evacuation drill records and corrective actions per site.
  • Keep a digital fire safety register, with every inspection filed against its asset or site.

Book a demo to see how MapTrack handles checklists.

Try MapTrack free for 30 days

Full access to every feature. No credit card required. Per-asset pricing so you scale as your fleet grows.

  • No credit card required
  • 30 days free trial
  • Cancel anytime

Less loss and downtime

“Doing monthly site audits in MapTrack has drastically reduced our equipment loss and downtime.”
Axis Services Group

Khalid El-Hussein

NSW Store Manager, Axis Services Group

What to include in a fire extinguisher 5-year hydrostatic test record

This fire extinguisher 5-year hydrostatic test record covers 10 key areas:

  • Extinguisher identification: asset number, serial number, type, capacity, manufacturer and date of manufacture.
  • Technician name and fire protection licence number.
  • Pre-test external condition assessment: corrosion, dents, pressure gauge, safety pin, tamper seal, hose and label.
  • Depressurisation and discharge confirmation with empty cylinder weight.
  • Internal inspection: cylinder walls, valve threads, siphon tube, internal coating.
  • Hydrostatic test: test pressure applied (kPa), elastic expansion (mL), permanent expansion (mL), percentage calculation.
  • Pass or condemn result with action taken.
  • Post-test recharge: correct agent, correct pressure, gauge verification, cylinder re-stamp.
  • Service tag attachment and fire safety register update.
  • Test certificate issuance confirmation.

How to use this fire extinguisher 5-year hydrostatic test record

  1. Conduct a thorough pre-test external condition assessment.: Inspect the cylinder for corrosion, dents, bulging and damage. Check the pressure gauge reading, safety pin, tamper seal, hose condition, nozzle and label legibility. Record the extinguisher type, capacity and date of manufacture. If the external condition shows severe damage, condemn without proceeding to hydrostatic test.
  2. Safely depressurise, discharge and disassemble the extinguisher.: Depressurise the cylinder safely following the manufacturer procedure. Discharge all remaining agent into an approved container. Remove the valve assembly and weigh the empty cylinder, recording the tare weight for comparison against manufacturer specifications.
  3. Perform a detailed internal inspection of the cylinder.: Use a borescope or light source to examine internal cylinder walls for corrosion, pitting, scoring and thinning. Inspect valve threads for damage. Check the siphon tube and dip tube for deterioration. Examine any internal coating or lining for delamination. If significant internal damage is found, condemn the unit without proceeding to hydrostatic test.
  4. Fill the cylinder with water and perform the hydrostatic pressure test.: Fill the cylinder completely with water, eliminating all air. Connect to calibrated hydrostatic test equipment. Pressurise to the specified test pressure and hold for a minimum of 60 seconds. Measure elastic expansion during pressurisation and permanent expansion after release. Calculate permanent expansion as a percentage of elastic expansion.
  5. Determine the result and complete post-test actions.: If permanent expansion exceeds 10% of elastic expansion, the extinguisher fails and must be condemned and destroyed by the technician. If it passes, drain and dry the cylinder thoroughly, reassemble the valve, recharge with the correct agent to the correct pressure, verify the gauge reads in the green zone, and re-stamp the cylinder with the new test date.
  6. Complete certification and update all records.: Attach a new service tag showing the test date and next due date. Update the building fire safety register with the test result. Issue a formal test certificate to the site fire warden or facility manager. Record condemned and destroyed units in the register with replacement details.

In MapTrack, you can manage fire safety inspections and equipment checks digitally. Each submission is stored as a timestamped PDF against the asset record.

Get the free templateEnter your email above to download the full fire extinguisher 5-year hydrostatic test record as a PDF.Back to download form

How often should you complete this checklist?

AS 1851-2012 sets six-monthly, yearly and five-yearly service for portable extinguishers, with a three-yearly item in clause 10.2.3. There is no single pressure-test interval for every extinguisher: what the five-yearly service involves, and whether the cylinder is pressure tested, depends on the type, and a CO2 cylinder is a gas cylinder with its own test regime, so ask your service provider what applies to each unit. The clock starts from the date of manufacture stamped on the cylinder, not from the date of installation. A monthly visual check between services is site practice, not an AS 1851 frequency. In MapTrack, you can set each extinguisher's test schedule against its asset record, and the assigned person gets an email in the week before each test falls due, across all your sites.

Frequently asked questions

If permanent expansion exceeds 10% of elastic expansion, the cylinder has plastically deformed and cannot safely contain pressure. It must be condemned immediately. The technician must physically destroy the cylinder, typically by drilling or cutting, to prevent it from being returned to service. A replacement extinguisher must be installed at the same location.

Hydrostatic testing must be done by a competent person (AS 1851-2012 clause 1.10) holding any licence or approval your state or territory requires, using calibrated test equipment with current certification. In NSW, inspection and testing that involves no specialist trade generally needs no licence, so check the technician's training and experience as well as any licence they hold.

The six-monthly service (AS 1851-2012 clause 10.4.1) is a visual and functional check covering gauge pressure, tamper seal, hose condition and mounting. A hydrostatic test is a pressure test that verifies the structural integrity of the cylinder itself, done at the five-yearly service (clause 10.4.3) where the extinguisher type calls for one. It requires complete discharge, internal inspection and pressurisation above normal operating pressure.

It can. CO2 extinguishers operate at much higher pressures and have thicker-walled cylinders, and a CO2 cylinder is a gas cylinder with its own inspection and test regime. Published test intervals for CO2 disagree with each other, so ask the technician who services your site what applies rather than working from one number. The test pressure for CO2 cylinders is also significantly higher.

AS 1851-2012 sets out routine service records, including records retention, in clause 1.16, and in NSW building owners must keep those records for at least 7 years. Keep the hydrostatic test certificate and test record for the extinguisher's full service life and for at least 7 years after the unit is condemned or replaced. The certificate must be available to the building owner, fire authority and certifier: it supports the Annual Fire Safety Statement (NSW) or annual essential safety measures report (Victoria), and in the ACT, records must be available to ACT Fire & Rescue within 48 hours of a request. If a cylinder is condemned and destroyed, keep the destruction record with the replacement unit's history.

Applicable regulatory standards

This template is a starting point. Check the current requirements that apply to your equipment, work and location. The template alone does not establish compliance.

  • AS 1851 Routine service of fire protection systems and equipment
  • AS/NZS 1841.1 Portable fire extinguishers - General requirements
  • National Construction Code (NCC/BCA) - Essential Safety Measures provisions
  • AS 2444 Portable fire extinguishers and fire blankets - Selection and location

Fire extinguisher 5-year hydrostatic test record preview

Fire extinguisher 5-year hydrostatic test record template preview showing fields and layout

The numbers behind this fire extinguisher 5-year hydrostatic test record

Every figure below is sourced and dated, so you can quote it in a toolbox talk, a budget case or a board paper without having to chase the original report.

Embed this free template on your website

Run an industry blog, trade association site, or training resource? Drop a preview of this free fire extinguisher 5-year hydrostatic test record straight into your page. The snippet is self-contained, needs no scripts, and links readers back to the full free template.

<div style="max-width:480px;font-family:system-ui,-apple-system,'Segoe UI',Roboto,sans-serif;border:1px solid #E5E7EB;border-radius:12px;padding:20px;background:#ffffff;">
  <p style="font-size:12px;font-weight:700;letter-spacing:0.05em;text-transform:uppercase;color:#071D49;margin:0;">Free template</p>
  <p style="font-size:18px;font-weight:700;color:#071D49;margin:6px 0 0;">Fire extinguisher 5-year hydrostatic test record</p>
  <ul style="margin:12px 0 0;padding-left:18px;color:#374151;font-size:14px;line-height:1.6;">
    <li style="margin:4px 0;">Extinguisher identification: asset number, serial number, type, capacity, manufacturer and date of manufacture.</li>
    <li style="margin:4px 0;">Technician name and fire protection licence number.</li>
    <li style="margin:4px 0;">Pre-test external condition assessment: corrosion, dents, pressure gauge, safety pin, tamper seal, hose and label.</li>
    <li style="margin:4px 0;">Depressurisation and discharge confirmation with empty cylinder weight.</li>
    <li style="margin:4px 0;">Internal inspection: cylinder walls, valve threads, siphon tube, internal coating.</li>
    <li style="margin:4px 0;">Hydrostatic test: test pressure applied (kPa), elastic expansion (mL), permanent expansion (mL), percentage calculation.</li>
  </ul>
  <p style="font-size:13px;color:#6B7280;margin:14px 0 0;padding-top:12px;border-top:1px solid #E5E7EB;">Free <a href="https://www.maptrack.com/templates/fire-extinguisher-5-year-test" style="color:#071D49;font-weight:600;text-decoration:none;">Fire extinguisher 5-year hydrostatic test record</a> by MapTrack</p>
</div>

Free to reuse, including commercially. This template is published under a Creative Commons Attribution 4.0 licence. Copy it, adapt it, put it on your own site or in your own docs. All we ask is that you credit MapTrack with a link back to this page. The snippet above already includes that credit, so if you use it as-is you’re covered.

Cite this template

Writing about this topic? You’re welcome to quote this checklist. Here’s the wording to use so your readers can find the original.

The MapTrack fire extinguisher 5-year hydrostatic test record contains 30 checks across 6 sections.

Short attribution
MapTrack Fire extinguisher 5-year hydrostatic test record, https://www.maptrack.com/templates/fire-extinguisher-5-year-test
Reference list
MapTrack. (2026). Fire extinguisher 5-year hydrostatic test record [Checklist template]. Retrieved from https://www.maptrack.com/templates/fire-extinguisher-5-year-test

Free to reuse with credit under a Creative Commons Attribution 4.0 licence. If you’d rather link straight to it, the page is https://www.maptrack.com/templates/fire-extinguisher-5-year-test.

Need to manage fire safety inspections and equipment checks digitally?

Register every asset in MapTrack, attach digital forms, and get a complete history of every inspection, service and compliance record.

Compliance and inspections · All templates · Pricing · Book a demo