To save as PDF: use your browser's PrintSave as PDF or Print to PDF. This test register prints as 2 pages (A4).

Test & Tag Register - Portable Electrical Equipment

In-service safety inspection & testing  ·  AS/NZS 3760

Company logo

PAGE 1 OF 2

Tester & Site Details

Visual Inspection Reference - check each item before testing

1. Plug - correct for application, pins straight, cover intact, no cracking or burn marks 4. Switches / controls - no physical damage, guards in place, no sign of overheating 2. Flex / cable - no cuts, abrasions, bare conductors or kinks; strain relief intact at plug and appliance end 5. Earth pin (Class I) - present, straight and intact; not removed or bypassed 3. Equipment body - no cracks, burn marks, liquid ingress, modifications or missing fasteners 6. Previous tag - remove and dispose of old tag; record item on new tag before attaching

Test Register - Page 1 of 2 (Items 1–12)

Visual: P = Pass  |  F = Fail. Record actual meter readings for IR (MΩ) and Earth (Ω). Enter N/A where test is not applicable for the equipment class. Result: P = Pass  |  F = Fail - failed items must be tagged out-of-service and listed on page 2. Class: I = earthed metal body  |  II = double insulated  |  III = extra-low voltage.

# Equipment description / Asset ID Location / Room Class Visual P/F IR (MΩ) Earth (Ω) Result P/F Next Test Due Notes
1
2
3
4
5
6
7
8
9
10
11
12
Test & Tag Register - Page 2 of 2
Site / Location
Test date
Tester

Test Register: Continued (Items 13–24)

# Equipment description / Asset ID Location / Room Class Visual P/F IR (MΩ) Earth (Ω) Result P/F Next Test Due Notes
13
14
15
16
17
18
19
20
21
22
23
24

Test Limits Reference - AS/NZS 3760 Minimum Pass Requirements

Test Class I - earthed (metal body, 3-pin with earth) Class II - double insulated (no earth pin) Class III - extra-low voltage (≤ 50 V AC)
Insulation resistance (IR) ≥ 1 MΩ ≥ 2 MΩ ≥ 0.25 MΩ
Earth continuity ≤ 1 Ω (total path resistance) N/A N/A
Polarity check Active and neutral correct Active and neutral correct N/A (typically)
Visual inspection Pass required for all classes: refer to visual inspection reference on page 1

Failed / Non-Conforming Items  (list any item with a Fail result: reference item # from register above)

Item # Equipment / fault description Action taken / reported to Cleared by / date

Declaration

I declare that I am a competent person (as defined in AS/NZS 3760) and that all electrical equipment listed in this register has been visually inspected and electrically tested on the date shown, using a calibrated test instrument. All results are recorded accurately. Items marked as Fail have been taken out of service, tagged accordingly, and reported as required. I understand this record must be retained for the period specified in AS/NZS 3760.

Tester Sign-off
Signature
Print name
Cert. / Licence no.
Date
Supervisor / Client Acknowledgement (optional)
Signature
Print name
Date