Smoke Detector Testing Checklist

Periodic testing and inspection record for smoke detection devices per AS 1851 and AS 1670.1

Company Logo
FORM-FIRE-SMK-01
System Details

Mark P (Pass), F (Fail), or N/A for each item. Monitoring station must be notified before and after testing.

# Inspection Item P F N/A Notes
Visual Inspection
1Detector housing clean, free from dust, paint, or contamination
2Detector firmly seated in base with no visible damage
3No obstructions within 500mm of detector (shelving, signage)
4LED indicator visible and functioning (steady/flash as applicable)
5Correct detector type installed for the environment
Functional Test
6Detector responds to approved test aerosol or smoke source
7Alarm signal received at fire indicator panel (FIP)
8Correct zone and address displayed on panel
9Associated alarm devices (sounders, strobes) activated
10Detector resets correctly after alarm cleared
Sensitivity
11Sensitivity reading within manufacturer specified range
12Drift compensation functioning (addressable systems)
13No detectors flagged for excessive contamination by panel
14Detectors within serviceable age limit (per manufacturer)
Wiring & Connections
15Wiring connections secure at detector base
16No visible damage to cabling or conduit
17Loop integrity test passed (addressable systems)
18Earth fault monitoring functioning on detection circuits
Compliance
19Monitoring station notified prior to testing
20System restored to normal and monitoring station advised
21Failed detectors tagged and replacement scheduled
22Test records entered in fire safety logbook

Declaration

I confirm that all smoke detectors have been tested in accordance with AS 1851 and AS 1670.1. Failed devices have been reported and isolated pending replacement. The detection system has been returned to full operational status.

Licensed Tester
Name
Signature
Date
Building Manager
Name
Signature
Date