Workplace fire prevention inspection per 29 CFR 1910.39 and Subpart L.
PAGE 1 OF 2
Inspection Items
Mark the applicable column for each item: P = Pass | F = Fail | N/A = Not applicable. Record notes for any F.
| # | Check | P | F | N/A | Notes / Action |
|---|---|---|---|---|---|
| Fire Prevention Plan (1910.39) | |||||
| 1 | Written fire prevention plan exists and is current | ||||
| 2 | Plan identifies all major workplace fire hazards | ||||
| 3 | Responsible personnel identified in the plan by name and role | ||||
| 4 | Plan accessible to all employees for review per 1910.39(b) | ||||
| 5 | Employee training on fire prevention plan completed and documented per 1910.39(d) | ||||
| Ignition Source Controls | |||||
| 6 | Hot work permits issued and controlled for all welding, cutting and brazing | ||||
| 7 | Smoking restricted to designated areas only, signage posted | ||||
| 8 | Heat-producing equipment has proper clearance from combustibles | ||||
| 9 | Electrical equipment in good condition, no overloaded circuits or damaged cords | ||||
| 10 | Static discharge controls in place where flammable vapors are present | ||||
| Flammable & Combustible Materials (1910.106) | |||||
| 11 | Flammable liquids stored in approved cabinets or storage rooms | ||||
| 12 | Container labeling correct and legible for all flammable materials | ||||
| 13 | Quantity limits for flammable liquids not exceeded in work areas | ||||
| 14 | Compressed gas cylinders stored upright, secured and segregated by type | ||||
| 15 | Secondary containment provided for bulk flammable liquid storage | ||||
| Housekeeping & Waste Management | |||||
| 16 | Combustible waste removed regularly, no excessive accumulation | ||||
| 17 | Oily rags stored in approved self-closing metal containers | ||||
| 18 | Combustible dust accumulations controlled (ducts, surfaces, equipment) | ||||
| 19 | Electrical rooms and panel areas free of combustible storage | ||||
| 20 | Exterior dumpsters and waste storage at least 20 ft from buildings | ||||
| # | Check | P | F | N/A | Notes / Action |
|---|---|---|---|---|---|
| Fire Protection Equipment (Subpart L) | |||||
| 21 | Fire extinguishers in designated locations, unobstructed and visible | ||||
| 22 | Monthly inspection tags current on all extinguishers | ||||
| 23 | Annual professional maintenance completed on all extinguishers | ||||
| 24 | Sprinkler heads have minimum 18 in. clearance, unobstructed | ||||
| 25 | Sprinkler control valves open, tamper seals intact | ||||
| 26 | Fire alarm pull stations accessible and unobstructed | ||||
| 27 | Emergency lighting functional (tested where accessible) | ||||
| Exit Routes & Emergency Action Plan (1910.38) | |||||
| 28 | Exit routes clear, unobstructed and wide enough for safe evacuation | ||||
| 29 | Exit signs illuminated and visible from all approach directions | ||||
| 30 | Exit doors unlocked during working hours, open in direction of travel | ||||
| 31 | Emergency action plan coordinated with fire prevention plan | ||||
| 32 | Assembly points designated, communicated and accessible | ||||
| Training & Documentation | |||||
| 33 | All employees trained on fire prevention plan responsibilities | ||||
| 34 | New employees trained within first week of hire | ||||
| 35 | Fire extinguisher training provided to designated employees | ||||
Hazards & Corrective Actions (list any item marked F: reference item # from checklist)
| Item # | Hazard description | Corrective action / reported to | Corrected by / date |
|---|---|---|---|
Declaration
I declare that I have completed this fire prevention inspection in accordance with OSHA 29 CFR 1910.39 and Subpart L requirements. I have reported any hazards or non-compliant conditions to the responsible party and understand that fire hazards presenting a recognized danger must be corrected before employees are permitted to work in the area.