Fire Extinguisher 5-Year Hydrostatic Test Record

Hydrostatic pressure test and service per AS 1851 Level 4

Your logo here
PAGE 1 OF 1
5-YEAR HYDROSTATIC TEST

Required every 5 years (water, foam, dry powder) or 10 years (CO2)

Important: Hydrostatic testing must be performed by a licensed fire protection technician with calibrated test equipment. Extinguishers that fail the hydrostatic test must be condemned and destroyed. Do not return a failed extinguisher to service.

Equipment and Test Details

# Inspection Item Method P / F Notes / Measurements
1. Pre-Test Condition Assessment
1Cylinder external condition (corrosion, dents, damage)INSPECT
2Pressure gauge readingINSPECT
3Safety pin and tamper sealINSPECT
4Hose and nozzle conditionINSPECT
5Label legibilityINSPECT
6Mounting bracket conditionINSPECT
2. Depressurisation and Discharge
7Depressurise cylinder safelyDISCHARGE
8Discharge all contentsDISCHARGE
9Remove valve assemblyDISCHARGE
10Weigh empty cylinder and recordMEASURE
3. Internal Inspection
11Internal cylinder walls (corrosion, pitting, scoring)INSPECT
12Valve thread conditionINSPECT
13Siphon tube condition (if fitted)INSPECT
14Dip tube conditionINSPECT
15Internal coating/lining (if applicable)INSPECT
4. Hydrostatic Pressure Test
16Fill cylinder with waterTEST
17Pressurise to test pressureTEST
18Hold for 60 seconds minimumTEST
19Measure elastic expansionMEASURE
20Measure permanent expansionMEASURE
21Permanent expansion must not exceed 10% of elastic expansion - PASS/FAILMEASURE
5. Post-Test and Recharge
22Drain and dry cylinder thoroughlyRECHARGE
23Reassemble valveRECHARGE
24Recharge with correct agent and pressureRECHARGE
25Verify pressure gauge in green zoneVERIFY
26Re-stamp cylinder with test dateRECORD
6. Certification
27Attach new service tagVERIFY
28Update fire safety registerRECORD
29Condemn and destroy if failedDISCHARGE
30Issue test certificateRECORD

Hydrostatic Test Results

Testing Technician

Site Fire Warden / Manager