Fire Door Inspection Checklist

Routine inspection record for fire-rated doors and frames per AS 1851 and AS 1905.1

Company Logo
FORM-FIRE-DR-01
Door Details

Mark P (Pass), F (Fail), or N/A for each item. Any failure on a fire door requires immediate corrective action to maintain fire compartmentation.

# Inspection Item P F N/A Notes
Door Leaf
1Door leaf free from damage, holes, or unauthorised modifications
2No warping, delamination, or swelling of door leaf
3Door opens and closes freely without binding or dragging
4Gap between door leaf and frame within specification (max 3mm)
5No wedges, holdback devices, or obstructions preventing closure
Frame & Hardware
6Frame securely fixed to wall with no gaps or movement
7Hinges secure, not worn, and correct number installed
8Latch engages fully into strike plate
9Hardware (handles, locks) compatible with fire rating
Seals & Intumescent
10Intumescent strips present and undamaged on all edges
11Smoke seals intact and providing continuous contact
12Threshold seal or drop seal functioning correctly
13No paint build-up compromising seal effectiveness
Closer Operation
14Door closer fitted and securely mounted
15Door self-closes fully from any open position
16Closing speed appropriate (not slamming, not too slow)
17Hold-open device (if fitted) connected to fire alarm system
18Hold-open device releases on alarm activation
Signage & Certification
19Fire door signage displayed on both sides ("Fire Door - Do Not Obstruct")
20"Do Not Hold Open" signage present (if no hold-open device)
21Compliance plate or tag affixed showing fire rating
22Service record tag current and up to date

Declaration

I confirm this fire door has been inspected in accordance with AS 1851 and AS 1905.1. Any defects identified compromise fire compartmentation and have been reported for immediate rectification. The door has been tagged accordingly.