Routine inspection and testing of emergency and exit lighting systems per AS 2293
PAGE 1 OF 2
| # | Inspection Item | OK/Fail | Notes |
|---|---|---|---|
| Exit Signs | |||
| 1 | All exit signs illuminated and clearly visible | ||
| 2 | Exit sign faces clean and not obscured | ||
| 3 | Directional arrows correct for egress path | ||
| 4 | Mounting secure, signs not damaged or faded | ||
| Emergency Luminaires | |||
| 5 | All luminaires illuminate on mains failure simulation | ||
| 6 | Light output adequate for escape path illumination | ||
| 7 | Diffusers and lenses intact and clean | ||
| 8 | Luminaire housings undamaged and secure | ||
| Battery Systems | |||
| 9 | Battery charge indicator showing healthy charge | ||
| 10 | Duration test passed (90 min for maintained fittings) | ||
| 11 | No battery swelling, leaking, or corrosion | ||
| 12 | Central battery system voltage within range (if fitted) | ||
| Switching and Control | |||
| 13 | Automatic changeover operates on mains interruption | ||
| 14 | Manual test switch accessible and functional | ||
| 15 | Control panel fault indicators clear (no active faults) | ||
| Certification Labels | |||
| 16 | Each fitting has a current test tag or label | ||
| 17 | Logbook entries up to date for previous tests | ||
| 18 | Compliance plate/certificate displayed (annual test) | ||
| Operational Test | |||
| 19 | Simulate mains failure and verify all fittings activate | ||
| 20 | Escape route illumination level visually acceptable | ||
| 21 | All fittings return to charge mode on mains restoration | ||
I confirm that all items have been inspected/completed as indicated above. Any defects or concerns have been noted and reported.