Emergency Lighting Inspection Checklist

Routine inspection and testing of emergency and exit lighting systems per AS 2293

Company
logo

PAGE 1 OF 2

Details
# Inspection Item OK/Fail Notes
Exit Signs
1All exit signs illuminated and clearly visible
2Exit sign faces clean and not obscured
3Directional arrows correct for egress path
4Mounting secure, signs not damaged or faded
Emergency Luminaires
5All luminaires illuminate on mains failure simulation
6Light output adequate for escape path illumination
7Diffusers and lenses intact and clean
8Luminaire housings undamaged and secure
Battery Systems
9Battery charge indicator showing healthy charge
10Duration test passed (90 min for maintained fittings)
11No battery swelling, leaking, or corrosion
12Central battery system voltage within range (if fitted)
Switching and Control
13Automatic changeover operates on mains interruption
14Manual test switch accessible and functional
15Control panel fault indicators clear (no active faults)
Certification Labels
16Each fitting has a current test tag or label
17Logbook entries up to date for previous tests
18Compliance plate/certificate displayed (annual test)
Operational Test
19Simulate mains failure and verify all fittings activate
20Escape route illumination level visually acceptable
21All fittings return to charge mode on mains restoration
Declaration & Sign-Off

I confirm that all items have been inspected/completed as indicated above. Any defects or concerns have been noted and reported.

Completed By
Reviewed / Approved By